首页 » Product » SZS Low Nitrogen Water Tube Gas Hot Water Boiler

SZS Low Nitrogen Water Tube Gas Hot Water Boiler

1. Water circulation utilizes a combination of forced and natural circulation;Boiler’s internal devices are rationally arranged to ensure the medium flowing in the tubes of a single loop will not cause steam and water to boil, with water velocity reasonable, safe and reliable.
2. Flue gas is controlled at around 10m/s, Adjacent tubes in convection tube bundles are connected with stainless steel flat bars to increase tube rigidity and prevent vibration during flue gas scouring. Guide plates are installed at flue bends to eliminate vibration during boiler operation.
3. Economizer (condenser) adopts patented technology with independent intellectual property rights, taking into account both heat transfer efficiency and operation resistance;
4. Boiler is surrounded by membrane type water-cooled walls on all sides, providing excellent sealing and preventing flue gas leakage, reducing heat loss and improving boiler efficiency.
5. With multiple layers of lightweight insulation cotton overlapped staggeredly, entire coating with heat-resistant paint, it makes heat dissipation loss≤0.15%. Membrane walls around the boiler form a large D-shaped furnace, and furnace volume heat load is ≤500kw, which is more conducive to low-nitrogen emissions with nitrogen oxides less than 30mg/Nm³.

Description

Product Name: Low Nitrogen Water Tube Gas Hot Water Boiler
Product Model: SZS Series
HS Code: 84021900
Manufacturing Standards: ASME/EU/GB
Packing: Boiler proper in nude packing, auxiliaries in steel frames for bulk vessel.
Application Range: 14MW≤Q≤29MW

Parameters

Model /
Parameters
SZS14-1.25/115/70-Q SZS17.5-1.25/115/70-Q SZS21-1.25/115/70-Q SZS29-1.6/130/70-Q
Rated thermal power (MW) 14 17.5 21 29
Rated working pressure (MPa) 1.25 1.25 1.25 1.6
Rated outlet water temperature (℃) 115 115 115 130
Rated return water temperature (℃) 70 70 70 70
Full water capacity (m³) 12.7 16.4 19.1 23.6
Design thermal efficiency (%) ≥96 ≥96 ≥96 ≥96
Exhaust gas temperature (℃) ≤90 ≤90 ≤90 ≤90
Design fuel Natural gas, city gas, gas, coke oven gas, 0# light diesel, etc.
Transport weight of the largest component (t) 45 50 62 70
Dimensions of boiler proper (L×W×H) (mm) 9820×3780×3850 9820×4070×4000 10700×4200×4000 13400×4200×4200
Dimensions after installation (L×W×H) (mm) 11240×6465×5085 11240×6765×5235 12120×7000×5330 14840×7215×5535
Interface diameter
(mm)
Outlet valve DN250 DN250 DN300 DN300(2×DN200+DN150)
Backwater valve DN250 DN250 DN300 2×DN200
Safety valve DN150+DN50 DN150+DN100 20×DN150 20×DN150
Blowdown valve DN50 DN50 DN50 DN50

Note:
1. The right to interpret this product belongs to Brit Thermal Energy Equipment Co., LTD., the design data may subject to changes without prior notice, the final design drawing shall prevail.
2. We can design and manufacture boilers with other parameters according to customers’ requirements.